Three-phase power calculator

Choose star or delta, enter the line voltage and either the current or the power, then read the kVA, kW, kvar, the power triangle and the per-phase values. Capacitor sizing, resonance and motor current are on the other tabs. Results are estimates for study and planning.

Three-phase power calculator calculates in your browser: the numbers you enter are never sent to a server. It is free and needs no sign-up.

How to use it

  1. Enter voltage, current and power factor In the Three-phase power calculator, open the Power tab, choose star or delta, enter line voltage, current or power, and power factor from 0.05 to 1. Choose lagging or leading; kVA, kW and kvar then appear.
  2. Check the power triangle For 400 V, 10 A and power factor 0.8 lagging, the page gives S = 6928.2 VA, P = 5542.6 W and Q = 4156.9 var. The triangle draws P, Q and S so you can check each side.
  3. Size the power factor correction On the Power factor correction tab, enter power, voltage, the old and new power factors and the frequency. For 100 kW, 400 V, 0.75 to 0.95 at 50 Hz, the page gives 55.32 kvar of correction.

Questions

What does the harmonic resonance estimate assume?

It ignores resistance and other capacitors. For a 1000 kVA transformer with 6% impedance, the estimate gives about the 17.36th harmonic. The band of ±10% is an experience threshold, not a standard requirement.

How is the motor current calculated?

Input current is output power divided by efficiency, then divided by the square root of 3, voltage and power factor. For an 11 kW motor at 400 V, 90% efficiency and power factor 0.85, the page gives about 20.75 A. It is an estimate: wiring and branch protection follow the table values of your local code, and overload protection follows the nameplate.

Are my inputs stored or uploaded?

No. All calculations run in your browser. A share link puts the inputs after the # sign, and that part is not sent to a server.